JB-QB-501 Fire alarm controller
Wall hanging form, Chinese LCD display
◆ Product Features
  • Chinese information display
  • Black box recording function
  • 250 bus device capacities
  • 5 manual external control units
  • Alarm address information secondary conversion precise positioning alarm location (Chinese and English input)
  • Field programmable fire alarm control
  • Send alarm information to fire display panel, fire control room graphic display device, etc.
  • Detector data quantification function (dimensionless)
  • Automatic identification of bus device types
◆ Technical specifications
Main power AC 220V (+10%~-15%) ,50HZ
Secondary power supply (backup power) DC 24V, 4AH (built-in)
Power consumption Monitoring state: ≤ 3W; Alarm state:≤10W (25 detectors are in fire state at the same time)
Basic monitoring capacity 1 loop, capacity 250 points
External control unit 5 units
External control unit contact capacity DC 30V,1A.
Inspection cycle ≤ 10 seconds (single point continuous inspection in case of abnormal situation)
Signal transmission distance ≤1000 meters (RVS-2×1.0mm2);
≤1500 meters (RVS-2×1.5mm2)
Alarm line wiring Two buses
Alarm bus voltage 24V (18V~26V)
Dimensions 365mm×89mm×305mm(L×W×H)
Operating temperature 0℃~55℃
Relative humidity ≤95%
Black box record number Can save the latest 999 records (including start, shutdown, reset, fire alarm, supervision, linkage and fault alarm and other information).
Linkage programming 100 (including or 1 logic, or 2 logic, and logic).
Position conversion capacity 1×250,
Each 10 Chinese characters or 20 English characters
Fire alarm output relay 1 pair (KA1, KA2),
Passive contact, closed in case of fire
Fire alarm delay output relay 1 pair (DA1, DA2),
Passive contact, delayed closing after fire
Fault output relay 1 pair (YA1, YA2),
Passive contact, closed in case of fault
Dimensions 365mm×305mm×89mm(L×W×H)
◆ Certificate

COPYRIGHT © 2018 Wuxi Brightsky Electronic Co.,Ltd. ALL RIGHT RESERVED.
ICP 11076333-1