Main power | AC 220V (+10%~-15%) ,50HZ |
Secondary power supply (backup power) | DC 24V, 4AH (built-in) |
Power consumption | Monitoring state: ≤ 3W; Alarm state:≤10W (25 detectors are in fire state at the same time) |
Basic monitoring capacity | 1 loop, capacity 250 points |
External control unit | 5 units |
External control unit contact capacity | DC 30V,1A. |
Inspection cycle | ≤ 10 seconds (single point continuous inspection in case of abnormal situation) |
Signal transmission distance | ≤1000 meters (RVS-2×1.0mm2); ≤1500 meters (RVS-2×1.5mm2) |
Alarm line wiring | Two buses |
Alarm bus voltage | 24V (18V~26V) |
Dimensions | 365mm×89mm×305mm(L×W×H) |
Operating temperature | 0℃~55℃ |
Relative humidity | ≤95% |
Black box record number | Can save the latest 999 records (including start, shutdown, reset, fire alarm, supervision, linkage and fault alarm and other information). |
Linkage programming | 100 (including or 1 logic, or 2 logic, and logic). |
Position conversion capacity | 1×250, Each 10 Chinese characters or 20 English characters |
Fire alarm output relay | 1 pair (KA1, KA2), Passive contact, closed in case of fire |
Fire alarm delay output relay | 1 pair (DA1, DA2), Passive contact, delayed closing after fire |
Fault output relay | 1 pair (YA1, YA2), Passive contact, closed in case of fault |
Dimensions | 365mm×305mm×89mm(L×W×H) |