J-SAP-501 Manual fire alarm button
The work is stable and reliable, with a wide range of applications.
◆ Product Features
  • No polarity two-bus transmission manual alarm signal between the controller
  • Stable and reliable work, wide application range
  • Uses address code programmer to write address, no longer use the dial switch
  • Reset by reset key, no need to replace operation panel
  • Unique rotary structure, easy to install and use
◆ Technical specifications
Technical standard Meet the requirements of GB 19880-2005
Operating Voltage DC18~26V
Monitor current ≤350uA
Alarm current ≤1.5mA
Alarm method Press the operation panel
Confirmation lamp (red) Flash when running, always on when alarm
Line system Two alarm buses: T+, T-
(Non-polar)
Operating temperature -10℃~+55℃
Relative humidity ≤95%
Dimensions (without base) 88mm×28mm×92mm(L×W×H)
Weight About86g
Color Red
◆ Wiring diagram

Wiring diagram for J-SAP-501 Manual fire alarm button base

Wiring instructions
1, 3 terminal: T+, T- alarm bus (non-polarity)

◆ Certificate

COPYRIGHT © 2018 Wuxi Brightsky Electronic Co.,Ltd. ALL RIGHT RESERVED.
ICP 11076333-1